Fire Systems, Inc - Atlanta, Georgia

 

Fire Systems FAQ

  :: Home ::

FAQ :: Code Requirements :: About Us :: Contact Us :: News :: Employment :: Fire Systems Links   

Fire Sprinkler Systems    
Fire Sprinkler Systems:
Installation | Inspections
   
Fire Alarms & Monitoring    
Fire Alarms & Monitoring:
Installation | Inspections
   
Portable Fire Extinguishers    
Portable Fire Extinguishers:
Installation | Inspections
   
Special Hazard - Clean Agent Systems    
Special Hazard - Clean Agent
Waterless Fire Protection:

Installation | Inspections
   
Restaurant Fire Systems    
Kitchen Hood Fire Systems:
Installation | Inspections
   
Emergency & Exit Lighting    
Emergency & Exit Lighting:
Installation | Inspections
   
Vehicle Fire Systems    

Mobile Equipment -
Vehicle Fire Systems:

Installation | Inspections

   

FIRE SYSTEMS, INC :: FAQ > Fire Alarms & Monitoring

< Back

FREQUENTLY ASKED QUESTIONS - FIRE ALARM SYSTEMS

Q. How often must I have my fire alarm tested?
A. As a general rule, most devices must be tested on an annual basis with a visual inspection required semi-annually.

The requirements for testing and inspections are defined in NFPA 72 (National Fire Alarm Code).  Check with your local AHJ (Authority Having Jurisdiction) for local requirements.
 
Q. What is the difference between a Conventional fire alarm system and an Addressable fire alarm system?
A. A Conventional Fire Alarm System is typically used in smaller applications. They are usually less expensive than an addressable system but have limitations regarding reporting the location of devices. A conventional system will let you know which zone is in alarm, but not necessarily which device. A zone may contain several smoke detectors or pull stations. You may know which area of the building the smoke detector or pull station is located in but you will not know the location of the device that is in alarm.

An Addressable Fire Alarm System can be programmed to indicate the exact device that is in alarm. A display on the front of the panel will indicate the device type and location. For example, the display will indicate photoelectric smoke detector in alarm in first floor corridor outside room 201. This information can be extremely vital in larger facilities. These panels can usually be networked with other panels on a campus or within a facility.

 
Q. What is a Sensitivity Test on a Smoke Detector and how often is it required?
A. Calibrated Sensitivity Testing - The calibrated sensitivity test is designed to verify that a detector is operating within its’ listed and approved sensitivity range.

Paragraph 10.4.3.2.4 of NFPA 72 lists the various alternative methods for testing sensitivity of a detector. Some intelligent fire alarm system manufacturers have listed their fire alarm control panels (FACP) for this purpose. Other panels may show the original sensitivity setting of the detector at the time of installation. Sensitivity measurements may include analog values, percent-per-foot and percent-of-alarm, though, not all sensitivity test devices will provide measurement.

Please note that sensitivity testing can also be performed with a device that is independent of the alarm system and, if the sensitivity test is performed by using a device that introduces smoke or surrogate smoke to the detector, the requirements for functional testing would be met. (Also note that, unlike functional tests, sensitivity tests may not be required or performed every year)

Frequency for Sensitivity Testing - In other than one- and two-family dwellings, sensitivity of smoke detectors and single- and multiple-station smoke alarms shall be tested in accordance with the requirements of NFPA 72 (The National Fire Alarm Code).
  • Sensitivity shall be checked within 1 Year After Installation.
  • Sensitivity shall be checked Every Alternate Year thereafter unless otherwise permitted by compliance with the appropriate section of NFPA 72.
  • After the second required calibration test, if sensitivity tests indicate that the device has remained within its’ listed and marked sensitivity range (or 4 percent obscuration light gray smoke, if not marked), the length of time between calibration tests shall be permitted to be extended to a maximum of 5 years.
 
Q. What is UL 864 and how does it affect my existing fire alarm system?
A. As long as a fire alarm system is functioning properly there is no requirement to replace it, even if it is a pre UL 864 panel. Replacement parts for these older panels are being phased out. If you have a failure on your system you will be required to replace the panel, but in most cases the devices currently installed will still be compatible with the replacement panel. It would be wise to budget for a replacement on some of the older model panels.

Click here for more information on UL 864 >

 

< Back to top

 

Please contact Fire Systems, Inc. for answers to any questions you may have on our Fire Protection products or services. We look forward to working with you!

SPRINKLER ... ALARM ... EXTINGUISHER ... CLEAN AGENT ... KITCHEN ... VEHICLE

 

Fire Systems, Inc. : 4700 Highlands Parkway : Smyrna, Georgia  30082
Email: Sales@FireSystems.net : Phone: (770) 333-7979 : Web Site: www.FireSystems.net