Fire Systems, Inc - Atlanta, Georgia

 

Dry Chemical & Wet Chemical Fire Codes

  :: Home ::

FAQ :: Code Requirements :: About Us :: Contact Us :: News :: Employment :: Fire Systems Links   

Fire Sprinkler Systems    
Fire Sprinkler Systems:
Installation | Inspections
   
Fire Alarms & Monitoring    
Fire Alarms & Monitoring:
Installation | Inspections
   
Portable Fire Extinguishers    
Portable Fire Extinguishers:
Installation | Inspections
   
Special Hazard - Clean Agent Systems    
Special Hazard - Clean Agent
Waterless Fire Protection:

Installation | Inspections
   
Restaurant Fire Systems    
Kitchen Hood Fire Systems:
Installation | Inspections
   
Emergency & Exit Lighting    
Emergency & Exit Lighting:
Installation | Inspections
   
Vehicle Fire Systems    

Mobile Equipment -
Vehicle Fire Systems:

Installation | Inspections

   

FIRE SYSTEMS, INC :: FIRE CODES > Dry Chemical & Wet Chemical Fire Codes


 

Dry Chemical Systems

Monthly

Quarterly

Semi-annual 

Annual

Other 

CODE

NFPA 17
  Maintenance         9-3.1 At least semiannually, maintenance shall be conducted in accordance with the manufacturer’s listed installation and maintenance manual.
  Container Test         9-5a. The following parts of dry chemical extinguishing systems shall be subjected to a hydrostatic pressure test at intervals not exceeding 12 years: a. Dry Chemical Containers
  Hose Test         9-5c. The following parts of dry chemical extinguishing systems shall be subjected to a hydrostatic pressure test at intervals not exceeding 12 years: c. Hose Assemblies
  Agent Examination         9-3.1d. Examination of the dry chemical (If there is evidence of caking, the dry chemical shall be discarded and the system shall be recharged in accordance with the manufacturer’s instructions.)
  Agent Replacement         9-5.2 Dry chemical agent removed from the containers prior to hydrostatic testing shall be discarded.

 

Wet Chemical Systems

Monthly

Quarterly

Semi-annual 

Annual

Other 

CODE

NFPA 17A

 

Maintenance

 

 

 

 

5-3.1.1

At least semiannually, maintenance shall be conducted in accordance with the manufacturer’s listed installation and maintenance manual.

 

Container Test

 

 

 

 

5-5a.

The following parts of wet chemical extinguishing systems shall be subjected to a hydrostatic pressure test at intervals not exceeding 12 years: a. Wet Chemical Containers

 

Hose Test

 

 

 

 

5-5c.

The following parts of wet chemical extinguishing systems shall be subjected to a hydrostatic pressure test at intervals not exceeding 12 years: c. Hose Assemblies

 

Agent Replacement

 

 

 

 

5-5.2

Wet chemical agent removed from the containers prior to hydrostatic testing shall be discarded.


Fire Code Requirements >>

<< Back to Top

SPRINKLER ... ALARM ... EXTINGUISHER ... CLEAN AGENT ... KITCHEN ... VEHICLE

 

Fire Systems, Inc. : 4700 Highlands Parkway : Smyrna, Georgia  30082
Email: Sales@FireSystems.net : Phone: (770) 333-7979 : Web Site: www.FireSystems.net