Emergency & Exit Lighting
|
|
Emergency Lighting |
Monthly |
Quarterly |
Semi-annual |
Annual |
CODE |
NFPA 101 |
|
|
Testing |
 |
|
|
|
7-9.3 |
A functional test shall be conducted on every
required emergency lighting system at 30-day
intervals for not less than 30 seconds. |
|
|
Annual Test |
|
|
|
 |
7-9.3 |
An annual test shall be conducted on every
required battery-powered emergency lighting system
for not less than 11/2 hours. Equipment shall be
fully operational for the duration of the test. |
|
|
Exit Signs/Lighting |
Monthly |
Quarterly |
Semi-annual |
Annual |
CODE |
NFPA 101 |
|
|
Visual Inspection |
 |
|
|
|
7-10.9.1 |
Exit signs shall be visually inspected for
operation of the illumination sources at intervals
not to exceed 30 days. |
|
|
Annual Test |
|
|
|
 |
7-10.9.2 |
Exit signs connected to or provided with a
battery-operated emergency illumination source,
where required in 7.10.4, shall be tested and
maintained in accordance with 7.9.3. |
|