CODE |
NFPA 10 |
|
|
Inspection |
|
|
|
|
|
4-3.1 |
Fire extinguishers shall be
inspected when initially placed in service and
thereafter at approximately 30-day intervals. |
|
|
Maintenance |
|
|
|
|
|
4-4.1 |
Fire extinguishers shall be
subjected to maintenance at intervals of not more
than 1 year, at the time of hydrostatic test, or
when specifically indicated by an inspection. |
|
|
6-Year Maintenance |
|
|
|
|
|
4-4.3 |
Every 6 years, stored-pressure fire
extinguishers that require a 12-year hydrostatic
test shall be emptied and subjected to the
applicable maintenance procedures. |
|
|
Hydrostatic Test |
|
|
|
|
|
5-2 |
Refer to Table 5-2. |
|
|
Pressurized Water |
|
|
|
|
|
|
5 Years |
|
|
Wetting Agent(s) |
|
|
|
|
|
|
5 Years |
|
|
AFFF Foam |
|
|
|
|
|
|
5 Years |
|
|
FFFP Foam |
|
|
|
|
|
|
5 Years |
|
|
Carbon Dioxide (CO2) |
|
|
|
|
|
|
5 Years |
|
|
Dry Chemical(s) |
|
|
|
|
|
|
12 Years |
|
|
Halogenated Agent(s) |
|
|
|
|
|
|
12 Years |
|
|
Hose Conductivity Testing |
|
|
|
|
|
4-4.1.2 |
A conductivity test shall be
conducted annually on all carbon dioxide hose
assemblies. |