Fire Systems, Inc - Atlanta, Georgia

 

Special Hazard - Clean Agent
Waterless Fire Protection Inspections

  :: Home ::

FAQ :: Code Requirements :: About Us :: Contact Us :: News :: Employment :: Fire Systems Links   

Fire Sprinkler Systems    
Fire Sprinkler Systems:
Installation | Inspections
   
Fire Alarms & Monitoring    
Fire Alarms & Monitoring:
Installation | Inspections
   
Portable Fire Extinguishers    
Portable Fire Extinguishers:
Installation | Inspections
   
Special Hazard - Clean Agent Systems    
Special Hazard - Clean Agent
Waterless Fire Protection:

Installation | Inspections
   
Restaurant Fire Systems    
Kitchen Hood Fire Systems:
Installation | Inspections
   
Emergency & Exit Lighting    
Emergency & Exit Lighting:
Installation | Inspections
   
Vehicle Fire Systems    

Mobile Equipment -
Vehicle Fire Systems:

Installation | Inspections

   

FIRE SYSTEMS, INC :: INSPECTIONS :: Special Hazard - Clean Agent Waterless Fire Protection

Special Hazard - Clean Agent Fire Suppression Systems

Special hazard suppression systems are required to be inspected in accordance with NFPA 72 and NFPA 2001. Our highly trained technicians can inspect and service all types of special hazard systems. Our software system will keep a record of when inspections are due so you never have to worry about being delinquent on required inspections. We can also provide training in the proper use and maintenance of your system so in a fire situation everyone will be prepared to respond appropriately.
 
Inspections are performed using Fire Systems, Inc. technicians, without sub-contracting. We do not depend on another company for our expertise, we use our own technicians to inspect and repair your special hazard system; this gives us better control over the quality of service we are able to provide. When you call Fire Systems, Inc. we put you in contact with an individual specifically trained to address your fire protection needs.

Watch the FM-200 Fire Suppression Video >

Inspection and Testing Requirements for Special Hazard Suppression Systems

 

SYSTEM TYPE

           

REQUIREMENT

 

Clean Agent Systems

 Monthly

Quarterly 

 Semi-annual

Annual

Other

Code

NFPA 2001

 

System Inspection

 

 

 

 

4-1.1

At least annually, all systems shall be thoroughly inspected and tested for proper operation by competent personnel. Discharge tests are not required.

 

System Test

 

 

 

 

4-1.1

(Same as above)

 

Weigh Cylinders

 

 

 

 

4-1.3

At least semiannually, the agent quantity and pressure of refillable containers shall be checked.

 

Container Test

 

 

 

 

4-2.1

U.S. Department of Transportation (DOT), Canadian Transport Commission (CTC), or similar design clean agent containers shall not be recharged without retesting if more than 5 years have elapsed since the date of the last test and inspection.

 

Hose Test

 

 

 

 

4-3.2.1

All hose shall be tested every 5 years.

 

Room Integrity

 

 

 

 

4-4

At least every 12 months, the enclosure protected by the clean agent shall be thoroughly inspected to determine if penetrations or other changes have occurred that could adversely affect agent leakage or change volume of hazard or both.

 

Carbon Dioxide Systems

 Monthly

Quarterly 

 Semi-annual

Annual

Other

Code

NFPA 12

 

System Inspection

 

 

 

 

1-11.1

At least every 30 days, an inspection shall be conducted to assess the system’s operational condition.

 

System Test

 

 

 

 

1-11.3.2

The following shall be verified by competent personnel at least annually using available documentation required in 1-7.2.6.

 

Weigh Cylinders

 

 

 

 

1-11.3.5

At least semiannually, all high-pressure cylinders shall be weighed and the date of the last hydrostatic test noted (see 1-9.5.1)

 

Container Test

 

 

 

 

1-9.5.1

High-pressure cylinders used in fire-extinguishing systems shall not be recharged without a hydrostatic test (and remarking) if more than 5 years have elapsed from the date of the last test. Cylinders continuously in service without discharging shall be p

 

Hose Test

 

 

 

 

1-11.2.1

All system hose including those used as flexible connectors shall be tested every 5 years in accordance with 1-11.2.

 

Halon 1301 Systems

 Monthly

Quarterly 

 Semi-annual

Annual

Other

Code

NFPA 12A

 

System Inspection

 

 

 

 

4-1.1

At least semiannually, all systems shall be thoroughly inspected, tested, and documented for proper operation by trained competent personnel. Tests shall be in accordance with the appropriate NFPA or Canadian standards.

 

Container Test

 

 

 

 

4-2.1

DOT, CTC, or similar design Halon 1301 cylinders shall not be recharged without a retest if more than five years have elapsed since the date of the last test and inspection.

 

Hose Inspection

 

 

 

 

4-3

All system hoses shall be examined annually for damage.

 

Hose Test

 

 

 

 

4-3.2

All hoses shall be tested every 5 years in accordance with 4-3.1.

 

Room Integrity

 

 

 

 

4-4

At least every 6 months the halon-protected enclosure shall be thoroughly inspected to determine if penetrations or other changes have occurred that could adversely affect halon leakage.


Special Hazard - Clean Agent Suppression Systems :: Installation >>

Fire Systems, Inc. is your source for Special Hazard - Clean Agent Waterless Fire Protection Systems in the metro Atlanta area. Contact us today for a free survey.