Sprinkler Systems |
Monthly |
Quarterly |
Semi-annual |
Annual |
Other |
Code |
NFPA 25 |
|
|
Inspection |
|
|
|
|
|
|
|
|
|
Gauges - Dry,
PreAction & Deluge |
|
|
|
|
 |
2-2.4.2 |
Gauges on dry, preaction, and deluge systems shall
be inspected weekly to ensure that normal air and
water pressures are being maintained. |
|
|
Gauges - Wet Pipe
Systems |
 |
|
|
|
|
2-2.4.1 |
Gauges on wet pipe sprinkler systems shall be
inspected monthly to ensure that they are in good
condition and that normal water supply pressure is
being maintained. |
|
|
Control Valves |
 |
|
|
|
 |
|
(See "Valves" below) |
|
|
Alarm Devices |
|
 |
|
|
|
2-2.6 |
Alarm devices shall be inspected quarterly to verify
that they are free of physical damage. |
|
|
Hydraulic Nameplate |
|
 |
|
|
|
2-2.7 |
The
hydraulic nameplate, if provided, shall be inspected
quarterly to verify that it is attached securely to
the sprinkler riser and is legible. |
|
|
Buildings |
|
|
|
 |
|
2-2.5 |
Annually, prior to the onset of freezing weather,
buildings with wet pipe systems shall be inspected
to verify that windows, skylights, doors,
ventilators, other openings and closures, blind
spaces, unused attics, stair towers, roof houses,
and low spaces |
|
|
Hangers/Bracing |
|
|
|
 |
|
2-2.3 |
Sprinkler pipe hangers and seismic braces shall be
inspected annually from the floor level. |
|
|
Pipe & Fittings |
|
|
|
 |
|
2-2.2 |
Sprinkler pipe and fittings shall be inspected
annually from the floor level. |
|
|
Sprinkler Heads |
|
|
|
 |
|
2-2.1.1 |
Sprinklers shall be inspected from the floor level
annually. |
|
|
Spare Sprinkler
Heads |
|
|
|
 |
|
2-2.1.3 |
The
supply of spare sprinklers shall be inspected
annually… |
|
|
Valves (All Types) |
|
|
|
|
|
|
(See "Valves" below) |
|
|
Testing |
|
|
|
|
|
|
|
|
|
Alarm Devices |
|
 |
|
|
|
2-3.2 |
Waterflow alarm devices including, but not limited
to, mechanical water motor gongs, vane-type
waterflow devices, and pressure switches that
provide audible or visual signals shall be tested
quarterly. |
|
|
Main Drain |
|
 |
|
|
|
|
(See "Valves" below) |
|
|
Antifreeze Solution |
|
|
|
 |
|
2-3.4 |
The
freezing point of solutions in antifreeze shall be
tested annually by measuring the specific gravity
with a hydrometer or refractometer and adjusting the
solutions if necessary. |
|
|
Gauges |
|
|
|
|
 |
2-3.2 |
Gauges shall be replaced every 5 years or tested
every 5 years by comparison with a calibrated gauge.
Gauges not accurate to within 3 percent of the full
scale shall be recalibrated or replaced. |
|
|
Sprinkler Heads |
|
|
|
|
 |
2-3.1.1 |
Where sprinklers have been in service for 50 years,
they shall be replaced or representative samples
from one or more sample areas shall be submitted to
a recognized testing laboratory acceptable to the
authority having jurisdiction for field service test |
|
|
Sprinkler Heads -
Extra High Temp |
|
|
|
|
 |
2-3.1.1 |
Exception No. 3*: Representative samples of
solder-type sprinklers with a temperature
classification of extra high [325°F (163°C)] or
greater that are exposed to semicontinuous to
continuous maximum allowable ambient temperature
conditions shall be tested |
|
|
Sprinkler Heads -
Fast Response |
|
|
|
|
 |
2-3.1.1 |
Exception No. 2: Sprinklers manufactured using fast
response elements that have been in service for 20
years shall be tested. They shall be retested at
10-year intervals. |
|
|
Maintenance |
|
|
|
|
|
|
|
|
|
Valves (All Types) |
|
|
|
 |
 |
|
(See "Valves" below) |
|
|
Obstruction
Investigation |
|
|
|
|
 |
10-2.2 |
Systems shall be examined internally for
obstructions where conditions exist that could cause
obstructed piping. If the condition has not been
corrected or the condition is one that could result
in obstruction of piping despite any previous
flushing procedures. |
|
|
Valves |
Monthly |
Quarterly |
Semi-annual |
Annual |
Other |
|
|
|
|
Inspection |
|
|
|
|
|
|
|
|
|
Control Valves |
|
|
|
|
 |
9-3.3.1 |
All
valves shall be inspected weekly. |
|
|
Alarm Valves |
 |
|
|
|
|
9-4.1.1 |
Alarm valves shall be externally inspected monthly. |
|
|
Check Valves |
|
|
|
|
 |
9-4.2.1 |
Valves shall be inspected internally every 5 years
to verify that all components operate properly, move
freely, and are in good condition. |
|
|
Preaction/Deluge
Valves |
|
|
|
 |
|
9-4.3.1.3 |
The
interior of the preaction or deluge valve and the
condition of detection devices shall be inspected
annually when the trip test is conducted. |
|
|
Dry Pipe
Valves/Quick Opening Devices |
|
|
|
 |
|
9-4.4.1.4 |
The
interior of the dry pipe valve shall be inspected
annually when the trip test is conducted. |
|
|
Backflow Prevention
Assemblies |
|
|
|
 |
|
9-6.1.2 |
All
backflow preventers installed in fire protection
system piping shall be tested annually… |
|
|
Testing |
|
|
|
|
|
|
|
|
|
Main Drain |
|
 |
|
|
|
9-2.6 |
A
main drain test shall be conducted quarterly at each
water-based fire protection system riser to
determine whether there has been a change in the
condition of the water supply piping and control
valves. |
|
|
Waterflow Alarm |
|
 |
|
|
|
9-2.7 |
All
waterflow alarms shall be tested quarterly in
accordance with the manufacturer’s instructions. |
|
|
Control Valves |
|
|
|
 |
|
9-3.4.1 |
Each control valve shall be operated annually
through its full range and returned to its normal
position. |
|
|
Preaction/Deluge
Valves |
|
|
|
 |
|
9-4.3.2.2 |
Each deluge or preaction valve shall be trip tested
annually at full flow in warm weather and in
accordance with the manufacturer’s instructions.
|
|
|
Dry Pipe
Valves/Quick Opening Devices |
|
|
|
 |
|
9-4.4.2.1 |
Each dry pipe valve shall be trip tested annually
during warm weather. |
|
|
Backflow Prevention
Assemblies |
|
|
|
|
|
9-6.2.1 |
All
backflow preventers installed in fire protection
system piping shall be tested annually… |
|
|
Maintenance |
|
|
|
|
|
|
|
|
|
Control Valves |
|
|
|
 |
|
9-3.5 |
The
operating stems of outside screw and yoke valves
shall be lubricated annually. |
|
|
Preaction/Deluge
Valves |
|
|
|
 |
|
9-4.3.3.2 |
During the annual trip test, the interior of the
preaction or deluge valve shall be cleaned
thoroughly and the parts replaced or repaired as
necessary. |
|
|
Dry Pipe
Valves/Quick Opening Devices |
|
|
|
|
|
9-4.4.3.2 |
During the annual trip test, the interior of the dry
pipe valve shall be cleaned thoroughly and parts
replaced or repaired as necessary. |